Parameter

<< Click to Display Table of Contents >>

Navigation:  Valve Firmware > Interface > Logic > Analog Input >

Parameter

Previous pageReturn to chapter overviewNext page

 

Parameter

Description

Analog Input

Enable

True means it is supported.

False means it is not supported

Value

Indicate the applied voltage

Used Value = (Value + User Offset) * User Factor

User Factor

1 default value for Input voltage 0 to 10V

UserFactor = 10 / ( MaxVolt – MinVolt )

 

Example: Input voltage 2V to 8V

10/(8-2) = 1.667 User Factor

User Offset

0 default value for Input voltage 0 to 10V

UserOffset = -MinVolt

 

Example: Input voltage 2V to 8V

-2.0 = User Offset

Functionality

The Functionality is depend on the Current Control Mode

Control Mode Learn: Pressure Limit [SFS]

Control Mode Pressure: Target Pressure

Control Mode Position: Target Position

For settings Pressure Limit [SFS] must be Settings, Learn Limit = True

Table  Parameter Analog Input