The Gain Factor effects: Stability, Response time
- Higher gain results in: faster response, higher over- undershoot of pressure
- Lower gain results in: slower response, lower over- undershoot of pressure
Adjustment procedure:
1.Start with Gain Factor 1.0
2.Open valve.
3.Control a typical pressure / flow situation.
4.Repeat from step 2 with lower (higher) Gain Factors until optimal pressure response is achieved and stability is ok.
|
Normally adjustments down to Gain Factors of 0.42 should lead to good results. Otherwise you may need to improve sensor connection. Refer to «Requirements to sensor connection». |
Below graph shows response when changing pressure setpoint command:

Below graph shows response when changing gas flow: